Cast Resin Transformer

Cast Resin Transformer From LS IS

Metal Clad Switchgear

Standards

LS CAST RESIN Transformers confirm to the
requirements of IEC 60076-11 (2004). However we can also meet the requirements of the following standards, upon request.

  • IEEE C57.12.01 (2005)
    General requirement for dry-type distribution and power transformers
  • CSA Standard C9-02 (R2007)
    Dry type transformers.
  • HD538.1,2,3(1995)
    3 Phase Dry type distribution transformers. 50Hz from 100kVA to 2500kVA
  • BS 7806 (1995)
    Dry type Power transformers
  • AS 2374 (1982)
    Power transformers

Standards

RatingSpecification
Installation place Indoor(Enclosure needed for outdoor)
Applicable standard KS C 4311, IEC 60076-11, IEEE C57.12.01
Frequency 60, 50
Insulation kind F type, H type
Coil temperature rise 100K, 125K
HV rated voltage(kV) 33, 22, 10, 6
HV tap voltage(V) 5 Taps (±2x2.5%)
LV rated voltage 400V
Angular displacement Dyn11
Impulse withstand voltage(kV) (HV/ LV) 145 / -
170 / -
95 / -
125 / -
60 / -
75 / -
40 / -
60 / -
Normal frequency withstand voltage(kV) (HV/ LV) 70 / 3 50 / 3 28 / 3 20 / 3
Rated capacity (kVA) up to 3150
EnclosureIP 2X, IP 3X, IP 4X

Specification

LS CAST RESIN Transformers are normally available with specification as follows:

  • Rated voltage
    HV COIL : up to 36kV
    LV COIL : up to 600V
  • Standard Tapping range : ± 2.5%, ± 5%
  • Power capacity
    Single phase : 20 ~ 2,000kVA
    Three phase : 50 ~ 15,000kVA
  • Frequency : 50Hz, 60Hz
  • % Impedance voltage
    IEC STD. : 4.0 ~ 8.0%
    IEEE STD. : 5.75 ~ 8.0%
  • Connections
    HV COIL : Delta
    LV COIL : Star with neutral point
  • Temperature class (According to IEC 60076-11)
    HV COIL and LV COIL : F CLASS
  • Conductor
    Aluminum (standard)
    Copper (optional)
  • Noise Level (according to NEMA Std.)

Features

  • Environmentally safe
  • Moisture proof
  • No partial discharge
  • Low noise
  • High overload capability
  • High impulse strength
  • Maintenance free
  • Fire resistant